Fan Cycling Frequently Asked Questions
Q. If my house has hydronic
baseboard heat and forced air central cooling, what do I do with the fan
cycling control Wt terminal (which is normally wired in parallel with the
heat line at the air handler).
A. If the heating system is other than forced
air, simply ignore the Wt terminal, do not connect the heat line to the
fan cycling control. Since the hydronic heating system does not operate
the central fan, it does not need to be connected to the fan recycling
control. The control will operate the fan periodically throughout the year
as set up with the Fan OFF and Fan ON times.
Q. I have a two story house with
the heating and cooling thermostat on the first level. The temperature in
upstairs rooms is inconsistent with the downstairs and we are not
comfortable throughout the house. Can the fan cycling control help me with
that problem?
A. Yes. The fan cycling control will
periodically operate the central system fan to re-average the indoor
environmental conditions (temperature, humidity, air quality) throughout
the zone it serves. In your case, that means that the upstairs air will
mix with the downstairs air to smooth out variations and give the
thermostat better feedback on the true average temperature of the house.
The same holds true for single story houses with open or closed rooms that
are not near the thermostat.
If you are still unsure, a good test you can try is to turn your
central blower from AUTO to ON for awhile. If you are satisfied with
continuous blower operation after a day or two, then the fan cycling
control will give you the same performance at reduced operating cost. You
can adjust the fan cycling control settings to optimize for your
situation (i.e. find the best Fan OFF and Fan ON times for you).
Q. Some rooms in our house can
be very uncomfortable depending on where the sun is, can the fan
cycling control solve that problem?
A. In most cases, yes. Similar to the question
above, fan cycling will smooth out temperature variations from room to
room by periodically mixing air from all parts of the house. The fan
cycling strategy operates the central blower if it has been inactive for a
period of time. This is effective in making rooms throughout the house
more comfortable whether the discomfort be due to variations in solar heat
gains as a function of time-of-day, or due to door closure, distance from
the thermostat, inadequate insulation, or poor duct design. Of course,
there are limitations, if the insulation is severely inadequate, or worse,
the duct design doesn?t allow much air flow to the uncomfortable space,
then the effectiveness will be diminished.
Q. My house has two central air
handlers. Do I need to use two fan cycling controls or can I make one to
operate both systems?
A. If you want fan cycling capability on both
units, then you need two controls. The control wiring for each air handler
unit needs to be isolated from the other.
Q. I am using
central-fan-integrated ventilation with fan cycling for my house that has
two air handlers. Should I install an outside air duct to the return of
both systems or just one?
A. It would be best to install a smaller outside
air duct to the return of both air handlers. Splitting the heating and
cooling load for ventilation air between the two systems will give better
performance and will give better distribution of ventilation air
throughout the house. If you have to choose only one system, choose the
one that serves the bedrooms since that is where people will be for the
longest time.
Q. I live in a humid cooling
dominated climate. My HVAC contractor tells me that drawing fresh air to
the return side off my cooling system blower will be too hard on my
cooling system. Is that true?
A. No, as long as the following is true. The air
distribution system (blower and ducts) should either be inside the
conditioned space or they should be well sealed with mastic or foil tape
so that the air leakage from the ducts to outside is less than 5% of the
air handler flow rate. The house should also be constructed to reduce the
random and unknown quantity of air leakage from outdoors, while allowing
the mechanical ventilation system to provide and distribute a known amount
of fresh air, from a known source, on a regular basis.
Q. I live in a cold climate. My
heating equipment supplier is concerned that an outside air duct into the
return side of my gas furnace may cause the furnace heat exchanger to
fail. Can you comment on that?
A. Furnace manufacturers put a lower limit on the
air temperature that their heat exchangers are exposed to. This is to
reduce condensing of combustion products in heat exchangers that were not
designed to be condensing heat exchangers, and to reduce expansion and
contraction of heat exchanger parts at startup and shutdown which could
lead to cracking. Usually the lower limit is about 55 F, which
incidentally suggests that simply setting the thermostat back below that
level (even without a fresh air duct) while the house is not occupied
could violate the manufacturers warranty.
All gas combustion heat exchangers get wet inside upon startup. This is
because the rate of water production is greater than the rate of
evaporation until the heat exchanger gets hot. The percentage of cold
outside air must be limited so that the heat exchanger can get hot.
Properly sized systems will run long enough to keep the heat exchanger
dry.
The first and only time this issue formally arose with
central-fan-integrated ventilation was with a contractor who said his
Carrier distributor would void the warranty if the air temperature at the
heat exchanger was below 60 F. After a brief discussion with the equipment
distributor and sending a mixed temperature chart to them, the issue was
over. The chart assumed an outside air fraction of 7% (which is what the
ventilation system was designed for), and showed that for a -25 F outdoor
temperature and a low 66 F inside temperature, the mixed air temperature
at the furnace was 60 F. While this met the manufacturers criteria, the
questions to them remained unanswered??Do you have test data to
support the 60 F criteria, and do you void your customer?s warranty if
they set the thermostat below 60 F when they leave the house for a
time??
I personally have never had first hand experience with a heat exchanger
failure due to low return air temperature. An engineering colleague and
practitioner, David Hill, of Vancouver British Columbia has, however, upon
investigation, those systems had outside air fractions of about 20%. I
recommend outside air fractions as follows:
| Climate |
Description |
Maximum outside air fraction |
| hot-dry and hot-humid |
average monthly temperature above 45 F year around |
13% |
| mixed-dry and mixed humid |
less than 4500 heating degree days (base 65 F) |
10% |
| cold |
between 4500 and 8000 heating degree days |
7% |
| very cold |
over 8000 heating degree days |
5% |
Actual vs. Real?
Q. I started to construct a
spreadsheet to see what the sensitivity of average ventilation run time
was, based on fan on/off times and vent damper open/closed times. I want
to look at this because it's not intuitively obvious what average
ventilation rates will be as outdoor temperatures fluctuate. As I got into
it, I realized that it gets pretty complicated, because fan run times
based on T-stat calls will vary depending on equipment sizing related to
the loads, thermostat deadband, and other factors. (I was intending to
look at this from a BIN perspective to see what the effects would be at
various temperatures).
It occurred to me that you may have done some of this analysis on your
own, I'm curious if you could share your experience and any analysis or
monitoring you've done, to help save my re-inventing something that's
already been done.
A. In the early to mid 1990's, after thinking of,
and working with many different ways to control outside air intake using a
ventilation system integrated with the central system air handler, I came
to the conclusion that what I call a "simply smart" approach was
best (especially for our production builder clients). Since my desired
approach was not available in the market, I developed a fan cycling and
outside air damper cycling controls. As your question illuminates,
"simple" usually requires some compromises that move away from
precision. The important question then becomes, how precise do you need to
be to get the desired result?
I agree, trying to simulate actual performance is very complicated
because there are so many variables and assumptions required. So to get at
the answer more believably I have tested and monitored the controls in
many houses to establish how much under- or over-ventilation would
normally occur due to the logic of the control and the varying cycle
periods of the heating and cooling equipment. I have found that over
daily, weekly, and monthly periods, the variation is less than 5% of the
ventilation design. That is, if you were shooting for a 33% ventilation
duty cycle (for example Fan OFF time=20 minutes and Fan ON time=10) then
the actual ventilation duty cycle would be within 28% and 38%.
Colleagues at an engineering and architectural consulting firm IBACoS
Inc., in Pittsburgh, PA in collaboration with the National Renewable
Energy Laboratory have used and evaluated the controls in homes and came
to the same general conclusion, that, over daily periods or greater, the
control provided the desired ventilation operation time within a few
percent.
The Canadian Housing and Mortgage Corporation also evaluated the fan
cycling control as part of a retrofit ventilation program and had only
good things to say about it. Please see a condensed version of their
Research Highlights Report from that study. Cases #6 and #10 used the
FanRecycler.
If you use a fan cycling and outside air damper cycling control (fan
recycling plus motorized outside air damper recycling), the variation is
only about 2%. The fan cycling control assures a minimum amount of
ventilation, while the outside air damper cycling control limits
ventilation to a maximum by closing the outside air damper after the air
handler blower has operated long enough to satisfy the ventilation design.
The damper also spring returns closed when the blower is de-energized,
closing the intentional hole to outside. This is the logical upgrade to
the fan cycling system. At this point, few of our production builders have
gone with the upgrade, since they are happy with the performance of the
fan cycling system. However, I think it is well worth the extra cost
(about $100 total cost difference for the control and installed damper),
especially for very cold and hot-humid climates.
I hope this has helped you. For additional information, look for the
May/June 2001 issue of Home Energy Magazine which will have an article on
ventilation and presents some monitored data from one of our clients
houses in Chicago. |